- Inputs: B/E/J/K/N/R/S/T, Pt 100, Pt 1000, Ni100, mV
- Potentiometer
- Three Custom Linearizations (Up to 96 Segments)
- 4-20mA Output(Reversible as 20-4mA)
- Better than 0.2% fs Accuracy
- Configurable by Android smartphone (using free of charge APP) or PC plus RF programmer
- Cold Junction Compensation Disabling
- Programmable Retransmitted Range
- Operating Temperature: -40-85C
- CE, EN 61326-1
- Calibrated According to EN 60584-1, EN60751
- In Stock for Fast and FREE Delivery
Ascon's ATT1 is a hockey puck style transmitter that can convert a thermocouple, RTD, or millivolt signal into a 4-20mA output. This powerful and configurable instrument can be programmed wirelessly with two different tools: an Android smartphone equipped with NFC capabilities and a free ATNFC APP or with a Windows PC by purchasing the NFC programmer/software package (part # TX-AS-AFC1-ATNFC).
Using these tools it is possible to configure the transmitter (sensor type, retransmitted range); store all the configurations you want; send a stored configuration to a new device; print all data (configuration or current measurement); see the current measured value.
Using the PC (equipped with TX-AS-AFC1-ATNFC) it is also possible to prepare and download your own custom linearization.
To Order the model below scroll to the top of the page then click ADD TO CART button |
DESCRIPTION | PART NUMBER |
Ascon's ATT1 Wireless, Din Head Mounted, Hockey Puck, Transmitter: T/C, RTD, mV | TX-AS-ATT1 |
ACCESSORY | |
NFC Program Kit for Windows PC | TX-AS-AFC1-ATNFC |
Software Download |
Visit the Ascon website to download the PC Configurator software and/or the Android Mobile App |
SPECIFICATIONS
SENSOR TYPES
PT100: Measuring range -200 to +800C, connection, 2,3,4 wire, accuracy 0.1% FS +/- uA
PT1000: Measuring range -200 to +800C, connection, 2 wires, accuracy 0.1% FS +/- uA
NI100: Measuring range -60 to +180C, connection, 2,3,4 wire, accuracy 0.5% FS +/- uA
TC B: Measuring range +40 to +1820, max accuracy +400 to +1820C
TC E Measuring range -200 to +940C
TC J Measuring range -200 to +1200C
TC K Measuring range -200 to +1340C
TC N Measuring range -200 to +1280C
TC R Measuring range -40 to +1760C
TC S Measuring range -40 to +1760C
TC T Measuring range -200 to +400C
mV input measuring range -10 to +70 mV
Accuracy: 0.1 % FS
Potentiometer low: 0 to 400 ohms, connection 2,3,4 wires, accuracy 0.1% FS +/- uA
Potentiometer high: 0 to 4 kohms, connection 2 wires, accuracy 0.1% FS +/- uA
GENERAL SPECIFICATION
RTD excitation current < 200 uA
RTD maximum wire resistance: 20 ohms per wire
TC input total accuracy: 0.2% FS +/- uA
CJ accuracy: +/-0.5C
CJ terminal drift: o.1C/C
Operating range: 7-20Vdc
Current output: 4-20 mA (2 wires)
Output resolution: 2 uA
Failure output: Selectable between 21 mA, 3.8 mA or any other value
Current output protection: 30 mA approx
Rejection: 50-60 Hz
Accuracy: Better than 0.2% range
Temperature drift: < 100ppm
Sampling time: 300 ms
Noise filters: no filter 200ms; med filter 1 s; strong filter 4 s
Protection: IP 20
CE, EN 60326-1
Operating temperature: -40 to +85C
Humidity: 30-90% @20C (non condensing)
Storage temperature: -40 to +105C
Connections: Screw terminals
Dimensions: 45 x 23 mm