- Isolated 4-20mA or 0-10Vdc Outputs
- Configurable for Humidity or Dew Point Temperature
- Configurable Ranges
- 3 Meter Cable Length
- IP65 Electronic Housing Rating
- Sensor Rated for -10 to 65°C and 145 PSI
RHT-XS humidity and transmitter features a highly accurate and stable sensor for measuring relative humidity and temperature. The measured values are converted into 4 to 20 mA or 0 to 10Vdc output signals(model dependent) which are linearly scaled to their readings. The RHT-XS includes an electronics module and remote sensor. The sensor is designed for non pressurized environments.
Configurable Parameters
The RHT-XS has several configurable parameters which are set by using the free downloadable software and the TxConfig-USB adapter. Configurable settings include:
- Humidity or Dew Point Temperature - The RHT-XS can be configured to transmit either humidity or dew point temperature
- Scalable Measurement Range/Output- Both the humidity and temperature measurement ranges are settable.
- Sensor Failure - Upon sensor failure the output may be set to go to either low or high.
.
| To Order the model below click on the link or scroll to the top of the page then click on ADD TO CART button |
| PART NUMBERS | DESCRIPTION |
| RHT-XS-MA | RHT-XS with 3 meter sensor cable and 4-20mA output |
| RHT-XS-MA | RHT-XS with 3 meter sensor cable and 0-10Vdc output |
| Accessories | |
| TxConfig-USB | USB Configuration Adapter |
| Downloads |
| RHT-XS Data Sheet |
| RHT-XS User Manual |
| SigNow Software |
SPECIFICATIONS
Humidity Measurement
Range: Programmable between 0 and 100 % RH or -100 and 103°C (-148 and 217.4 °F) for dew point.
Accuracy: 3% (refer to diagram)
Response Time: 8 seconds @25°C (in fairly still air)
Temperature Measurement
Range: Programmable between -40 and 120°C
Accuracy: 0.5°C (refer to diagram)
Response Time: up to 30s (in fairly still air)
General
Outputs: 4 to 20 mA or 20 to 4 mA, 2-wire type, loop-powered (current output versions), or 0 to 10 V (voltage output versions)
Output Resolution: 0.0008 mA or 0.003 V
Power Supply: 12 to 30 Vdc
Isolation: Outputs are isolated from one another
Maximum Load Resistance: (Vdc-12)/0.02 where Vdc = Power supply in Volts.
Electronic Module Protection: IP65
Sensor Protection: IP40
Electronic Module Operating Limits: -10 to 65°C, 0 to 95%RH
Sensor Operating Limits: -10 to 65°C, 0 to 100%RH
Sensor Cable Length: 3m
Certifications: CE Mark
IMPORTANT
The sensor may be damaged or lose calibration if it is exposed to aggressive atmospheres with high concentrations of as Chloride Acid, Nitride Acid, Sulfuric Acid and Ammonia. Acetone, Ethanol and Propylene Glycol may also cause measurement damage.