N1500 - Universal Process Indicator, 1/8 DIN

Free Shipping! - USA Orders Over $75

Customer Reviews
N1500 - Universal Process Indicator, 1/8 DIN
N1500 - Universal Process Indicator, 1/8 DIN

N1500 - Universal Process Indicator, 1/8 DIN

Regular price $171.00 Sale SKU:N1500-2R
3 In stock* Ships in 1 week, if NOT in stock
* ships same or next day


  • Input Type: Thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0 -50 mV, 0-5 Vdc, 0-10 Vdc, 4-20 mA No Linear, 0-20 mA Custom Linear, 4-20 mA Custom Linear, 0-20 mA Custom No Linear, 4-20 mA Custom No Linear
  • Analog Output: 0-20 mA or 4-20 mA (Optional) - Electrically Isolated
  • Dimensions: 96 x 48 x 92 mm (1/8 DIN)
  • Display: 7-segment LED, 6-digit with 17 mm Height
  • Custom Linearization: 30 points for Non-Standard Sensors
  • Digital Input: Operates as a Key for Hold, Peak Hold and Maximum/Minimum Reset
  • Alarms: Up to 4 Alarms
  • Alarm Types: Minimum, Maximum, Minimum Differential, Maximum Differential, Differential Out of Range, Differential within Range, and Open Sensor.
  • Timer Function: Alarms with Delay, Pulse, or Oscillator Timing.
  • Auxiliary Power Supply: 24 Vdc
  • Optional: 2 Relays, Analog Output (4-20 mA or 0-20 mA)
  • Communication: RS485 Modbus RTU Optional
  • Math Function: Square Root
  • Safety: Password Protected Configuration
  • Approvals: CE, UL and cUL


N1500 universal process indicator works at fast sampling rate, which ensures high-performance indication and reaction to fast processes dynamics. With 6 digits for high-resolution variables and the 17mm height display, N1500 provides clear view, making it easier for operators to read and diagnose from a distance.

Universal Input
The N1500 can accept most process sensors and signals. It works with thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0 -50 mV, 0-5 Vdc, 0-10 Vdc, 4-20 mA no linear, 0-20 mA custom linear, 4-20 mA custom linear, 0-20 mA custom no linear, 4-20 mA custom no linear.

Analog Output
The N1500 offers 0-20 mA or 4-20 mA (optional) output.

Alarms
The N1500 timer function performs wide action capabilities through alarms for safety interlock logic. It offers 2 alarms (4 optionally) and has the following alarm functions – Minimum, maximum, minimum differential, maximum differential, differential out of range, differential within range, and open sensor.

Fast Sampling Rate
The N1500 has a fast sampling rate of 5 samples per second for Pt100 and Thermocouples and 15 samples per second for 0-50 mV, 4-20 mA, 0-5 V and 0-10 V. This fast sampling rate makes this controller ideal for dynamic processes.

Protection and Safety
The N1500 was designed with anti-flame material UL94 V-2.

 To Order the model below scroll to the top of the page then  click on ADD TO CART button
N1500-2RIn Stock N1500 Universal Indicator 2 relays
N1500-2R-24V N1500 Universal Indicator, 2 relays, 24V power
N1500-2R-420MA N1500 Universal Indicator; 2 relays, 4-20 mA output
N1500-4R N1500 Universal Indicator, 4 relays
N1500-4R-24VIn Stock N1500 Universal Indicator, 4 relays, 24V power
N1500-4R-420MA N1500 Universal Indicator; 4 relays, 4-20 mA output, RS485
N1500-4R-420MA-24V N1500 Universal Indicator, 4 relay, 4-20 mA, 24V power, RS485

 

 Downloads
N1500 User Manual
N1500 Data Sheet

 

SPECIFICATIONS

Size
Dimensions: 
48 x 96 x 92 mm (1/8 DIN)
Approximate weight: 250 g
Panel Cut Out: 45 x 93 mm (+0.5 -0.0 mm)

Power
Power Supply: 
100 to 240 Vac/dc ±10 %, 50/60 Hz
Optional 24 V: 12 to 24 Vdc / 24 Vac (-10 % / +20 %) Max
Max. Consumption: 7.5 VA

Environmental Conditions
Operating Temperature: 
5 to 50 °C
Maximum RH: 80 % up to 30 °C

  • For temperatures above 30 ºC, decrease 3 % per °C
  • Installation category II, pollution degree 2; altitude < 2000 m

Input
Internal Resolution: 
128000 levels
Temperature: 
1 / 0.1
Other Measures: 
1 / 0.1 / 0.01 / 0.001 / 0.0001 
Input Sample Rate:

  • 5 per second for Pt100 and T/C
  • 15 per second to 0-50 mV, 4-20 mA, 0-5 V and 0-10 V

Accuracy:
Thermocouple Accuracy:

  • J, K, T, N: 0.25 % of span ±1 °C
  • E, R, S, B: 0.25 % of span ±3 °C

Pt100 Accuracy: 0.2 % of span
mA, mV, V Accuracy: 
0.2 % of span

Input Impedance:
0-50 mV, Pt100 and Thermocouples: 
>10 MΩ
0-5 V, 0-10 V: >1 MΩ
0-20 mA, 4-20 mA: 15 Ω (+2 Vdc @ 20 mA)

 