- Input Type: Thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0 -50 mV, 0-5 Vdc, 0-10 Vdc, 4-20 mA No Linear, 0-20 mA Custom Linear, 4-20 mA Custom Linear, 0-20 mA Custom No Linear, 4-20 mA Custom No Linear
- Analog Output: 0-20 mA or 4-20 mA (Optional) - Electrically Isolated
- Dimensions: 96 x 48 x 92 mm (1/8 DIN)
- Display: 7-segment LED, 6-digit with 17 mm Height
- Custom Linearization: 30 points for Non-Standard Sensors
- Digital Input: Operates as a Key for Hold, Peak Hold and Maximum/Minimum Reset
- Alarms: Up to 4 Alarms
- Alarm Types: Minimum, Maximum, Minimum Differential, Maximum Differential, Differential Out of Range, Differential within Range, and Open Sensor.
- Timer Function: Alarms with Delay, Pulse, or Oscillator Timing.
- Auxiliary Power Supply: 24 Vdc
- Optional: 2 Relays, Analog Output (4-20 mA or 0-20 mA)
- Communication: RS485 Modbus RTU Optional
- Math Function: Square Root
- Safety: Password Protected Configuration
- Approvals: CE, UL and cUL
N1500Ā universal process indicator works at fast sampling rate, which ensures high-performance indication and reaction to fast processes dynamics. With 6 digits for high-resolution variables and the 17mm height display,Ā N1500Ā provides clear view, making it easier for operators to read and diagnose from a distance.
Universal Input
The N1500 can accept most process sensors and signals. It works with thermocouplesĀ J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0 -50 mV, 0-5 Vdc, 0-10 Vdc, 4-20 mA no linear, 0-20 mA custom linear, 4-20 mA custom linear, 0-20 mA custom no linear, 4-20 mA custom no linear.
Analog Output
The N1500 offersĀ 0-20 mA or 4-20 mA (optional) output.
Alarms
The N1500 timer function performs wide action capabilities through alarms for safety interlock logic. It offers 2 alarms (4 optionally) and has the following alarm functions āĀ Minimum, maximum, minimum differential, maximum differential, differential out of range, differential within range, and open sensor.
Fast Sampling Rate
The N1500 has a fast sampling rate ofĀ 5 samples per second for Pt100 and Thermocouples andĀ 15 samples per second for 0-50 mV, 4-20 mA, 0-5 V and 0-10 V. This fast sampling rate makes this controller ideal for dynamic processes.
Protection and Safety
The N1500 was designed with anti-flame material UL94 V-2.
| Ā To OrderĀ the model below scroll to the top of the pageĀ thenĀ click onĀ ADD TO CARTĀ button |
| N1500-2R |
N1500 Universal Indicator 2 relays |
| N1500-2R-24V | N1500 Universal Indicator, 2 relays, 24V power |
| N1500-2R-420MA |
N1500 Universal Indicator; 2 relays, 4-20 mA output |
| N1500-4R | N1500 Universal Indicator, 4 relays |
| N1500-4R-24V |
N1500 Universal Indicator, 4 relays, 24V power(close out sale) |
| N1500-4R-420MA | N1500 Universal Indicator; 4 relays, 4-20 mA output, RS485 |
| N1500-4R-420MA-24V | N1500 Universal Indicator, 4 relay, 4-20 mA, 24V power, RS485 |
Ā
| Ā Downloads |
|
N1500 User Manual |
| N1500 Data Sheet |
Ā
SPECIFICATIONS
Size
Dimensions:Ā 48 x 96 x 92 mm (1/8 DIN)
Approximate weight:Ā 250 g
Panel Cut Out:Ā 45 x 93 mm (+0.5 -0.0 mm)
Power
Power Supply: 100 to 240 Vac/dc ±10 %, 50/60 Hz
Optional 24 V:Ā 12 to 24 Vdc / 24 Vac (-10 % / +20 %) Max
Max. Consumption:Ā 7.5 VA
Environmental Conditions
Operating Temperature: 5 to 50 °C
Maximum RH: 80 % up to 30 °C
-
For temperatures above 30 ºC, decrease 3 % per °C
- Installation category II, pollution degree 2; altitude < 2000 m
Input
Internal Resolution:Ā 128000 levels
Temperature:Ā 1 / 0.1
Other Measures:Ā 1 / 0.1 / 0.01 / 0.001 / 0.0001Ā
Input Sample Rate:
- 5 per second for Pt100 and T/C
- 15 per second to 0-50 mV, 4-20 mA, 0-5 V and 0-10 V
Accuracy:
Thermocouple Accuracy:
- J, K, T, N: 0.25 % of span ±1 °C
- E, R, S, B: 0.25 % of span ±3 °C
Pt100 Accuracy:Ā 0.2 % of span
mA, mV, V Accuracy:Ā 0.2 % of span
Input Impedance:
0-50 mV, Pt100 and Thermocouples:Ā >10 Mā¦
0-5 V, 0-10 V:Ā >1 Mā¦
0-20 mA, 4-20 mA: 15 ⦠(+2 Vdc @ 20 mA)
Ā