TxIsoRail - DIN Rail Mount Isolated Temperature Transmitter

Free Shipping! - USA Orders Over $75

Customer Reviews
TxIsoRail - DIN Rail Mount Isolated Temperature Transmitter

TxIsoRail - DIN Rail Mount Isolated Temperature Transmitter

Regular price $103.00 Sale SKU:TXISORAIL-010V
39 In stock* Ships in 3-4 weeks, if NOT in stock
* 10 available for immediate shipment, 29 ship in 2-3 days

  • Programmable Input: Thermocouples Type J, K, T, E, N, R, S, B, Pt100 RTD, 0-50 mV, 0-20 mA, 4-20 mA and 0-10 V
  • 1000 Vac Isolation for 1 Minute Between Sensor Input and 4-20 mA Output
  • DIN Rail Mount Unit
  • Configuration with a PC via TxConfig Interface
  • User Programmable Working Range 
  • 2-Wire Loop Powered 4-20 mA or 20-4 mA Output
  • 2 or 3-Wire Pt100 Input with Linearized Output
  • Cold Junction Compensation for Thermocouples
  • Manual Zero (Offset) Adjustment can be done by Means with 1 Front Key in the TxIsoRail
  • Sensor Failure Protection: Programmable Burnout Upscale or Downscale

TxIsoRail is fully programmable isolated temperature transmitter for Pt100 and thermocouple industrial sensors. It can be easily configured for input type and working range through an interface cable connected to a PC USB port.

Why use isolated transmitters?
Isolated transmitters protect the electrical instruments by eliminating ground loop effects and reduce substantially the undesirable interferences and instabilities in sensor measurements.

Programmable Input
The TxIsoRail can be programmed for a variety of industrial applications. It can accept thermocouples (types J, K, T, E, N, R, S and B), PT100 RTDs, 0-50 mV, 0-20 mA, 4-20 mA and 0-10 V.

Optional PC Configuration via TxConfig
The TxIsoRail can be configured through an interface cable connected to a RS232 PC port with the configurator software TxConfig. This software allows for users to easily configure the input type, desired working range, and necessary upscale or downscale protections.  For configuration via a USB port we offer the TxConfig-USB USB configuration adapter.


 To Order  click on the model below (or scroll to the top of the page and select the model from the drop down box) then ADD TO CART button
 PART NUMBERS DESCRIPTION
TXISORAIL-420MAIn Stock TxIsoRail with 4-20mA Output (requires optional TxConfig-USB for configuration)
TXISORAIL-010VIn Stock TxIsoRail with 0-10Vdv Output (requires optional TxConfig-USB for configuration)
ACCESSORIES
TxConfig-USB USB Configuration Adapter

 

 Downloads
TxIsoRail Data Sheet
TxIsoRail 4-20 mA User Manual
TxIsoRail 0-10 V User Manual

 

SPECIFICATIONS

Input:
Thermocouples - Types J, K, R, S, T, N, E and B to IEC 60584 (ITS-90). Impedance > 1 MΩ
pt100Excitation: 180 µA, 2 or 3-wire connection (for 2-wire sensors, tie, terminals 2 and 3 together). α= 0.00385, according to IEC 60751 (ITS-90).
Voltage0 to 50 mVdc, 0 to 10 Vdc. Impedance >> 1 MΩ. * Note: 0-10 Vdc input type requires an internal jumper switching. 0 to 20 mA, 4 to 20 mA. Impedance 15.0 Ω (+ 1.9 Vdc).

 Sensor Type Range Minimum Measurement Span
Thermocouple K -150 to 1370 °C / -238 to 2498 ºF 100 °C
Thermocouple J -100 to 760 °C / -148 to 1400 ºF 100 °C
Thermocouple R -50 to 1760 °C / -58 to 3200 ºF 400 °C
Thermocouple S -50 to 1760 °C / -58 to 3200 ºF 400 °C
Thermocouple T -160 to 400 °C / -256 to 752 ºF 100 °C
Thermocouple N -270 to 1300 °C / -454 to 2372 ºF 100 °C
Thermocouple E -90 to 720 °C / -130 to 1328 ºF 100 °C
Thermocouple B 500 to 1820 °C / 932 to 3308 °F 400 °C
Pt100 -200 to 600 °C / -328 to 1112 ºF 40 °C
Voltage 0 to 50 mV 5 mV
Voltage * 0 to 10 V 1 V
Current 0 to 20 mA 2 mA
Current 4 to 20 mA 2 mA

 

Output: 2-wire 4-20 mA, linear with respect to the measured signal

Resolution: 0.001 mA (14 bits)

Total Accuracy: Better than 0.3 % of the maximum span for thermocouples and 0.2 % for Pt100 and voltage

Response Time: < 500 ms

Isolation: Between the sensor and the 4-20 mA loop (1000 V / 1 min)

Power Supply: 12 to 35 Vdc, across the transmitter

Maximum Load (RL): RL (max.)= (Vdc – 12) / 0.02 [Ω] Were: Vdc= Power supply voltage

Operating Temperature: -40 to 85 °C

Humidity: 0 to 90 % UR

Electromagnetic Compatibility: EN 50081-2, EN 50082-2

Internal protection against polarity inversion

Cold junction compensation for thermocouples